1.4 Configure using the PQ Online settings wizard
☐
We recommend to select new setting to ensure good default values.
☐
Select connection method corresponding with 1.3.1 above
☐
Enter PT and CT ratio
☐
Select measuring standard EN50160
☐
1.4.1
Check main settings in Measure Configuration Summary. If you want to
change something go to
.
☐
1.4.2 Enter a setting Name
☐
1.4.3 You can save this configuration to a file for future use
☐
1.4.4 Finish the wizard and update the meter active settings
☐
Channel U4
1.4.13 Is U4 used? YES _____ NO ____ If NO, skip to 2.0.
☐
1.4.14
Go to advanced->Disturbances->Voltage trig. Select suitable U4 sag/swell
trig. Recommended trig/Uref=10%
If ground fault monitoring select ca 10% of nominal voltage.
Note! Value is stated in
.
☐
Channel I4
1.4.16 Is I4 used? YES ________ NO ________ . If no skip next step.
☐
Go to advanced->Disturbances->Current trig. Select suitable I4 trig level.
Note! Value is stated in
.
☐