Page 28
POWERING TECHNOLOGY
Manual No. aspiro2u-3
aspiro2u_m23-man-rev3-0516.indd
NOTE The temperature compensation factor can be set only for temperature sensor 1.
Ambient Temperature
Temperature sensor 2 allows a second temperature reading, most commonly the ambient
temperature around the system. Place the sensor as required.
The temperature is displayed in the External Measurements menu in the ACC controller or
in PowCom™ software.
NOTE Temperature sensor 2 can be activated only in the systems with the ACC
controller installed.
4.12 Rectier Installation
Rectier module should be installed starting from the bottom left position in the rectier
shelf.
Rectier Installation:
1. Place the rectier module in the mounting slot with handle facing out.
2. Slide the rectier module into the slot until it contacts the interface connection at the rear
of the shelf.
3. a) For XR04.48/XR08.48 fully insert the rectier by pushing it into the shelf, fasten the
rectier in the slot and tighten the screw with a screw driver.
b) For XPGe12.48 fully insert the rectier by pushing the handle towards the shelf. The
rectier handle will rise up and lock the rectier into position.
NOTE Ensure that the rectier handle is in the OPEN position (forms 35-40° angle with
rectier body) before inserting the module into the slot.
4. Repeat steps 1 to 3 if more rectiers are to be installed.
XR04.48 & XR08.48 XPGe12.48
Figure 4-14 Rectier Installation