DM2010 Manual Call Point Installation Sheet
EN DA ET IT LT LV PL SV
1
2
EN: Installation Sheet
Description
This document includes installation information for UTC Fire &
Security DM2010 manual call points. These manual call points
are designed for use in UTC Fire & Security Aritech analogue
addressable fire alarm systems and include models for indoor
and outdoor use.
Installation
Caution: This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any other
applicable local authority laws.
Electrical connections
Connect to the DM2010 connection block (Figure
2) as follows:
1. Line in (positive)
2. Line out (positive)
3. Line in (negative)
4. Line out (negative)
Addressing
Use the DIP switch (Figure 1) to allocate a device address
from 1 to 128 (see page 8).
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Voltage 17 to 28 VDC
Current consumption
Standby
Alarm
max. 250 ųA
max. 2.5 mA
Cable size
Minimum
Maximum
0.8 mm
2
2.5 mm
2
IP rating
DM2010, DM2010-18
DM2010E, DM2010E-18
IP24D
IP67
Operating environment
Operating temperature
Storage temperature
Relative humidity
−10°C to +70°C
−20°C to +70°C
10% to 95% noncondensing
Dimensions (W × H × D)
DM2010, DM2010-18
DM2010E, DM2010E-18
89 x 93 x 27.5 mm [1]
97.5 x 93 x 27.5 mm [1]
Weight 187 g