Table 63: AI low protection settings
Index Parameter Min Max Unit Default ID Description
P3.9.8.1
Analogue Input Low
Protection
0 2 767
0 = No protection
1 = Protection enabled
in Run state
2 = Protection enabled
in Run and Stop state
P3.9.8.2
Analogue Input Low
Fault
0 5 0 700
0 = No action
1 = Alarm
2 = Alarm + preset
fault frequency
(P3.9.1.13)
3 = Alarm + previous
frequency reference
4 = Fault (Stop accord-
ing to stop mode)
5 = Fault (Stop by
coasting)
PARAMETERS MENU VACON · 157