Table 119: Parameter ID307 selections
Applic.
1 to 4 5 and 7 6
Sel.
0 Not used Not used Not used
1 Output freq. (0—f
max
) Output freq. (0—f
max
) Output freq. (0—f
max
)
2 Freq. reference (0—f
max
) Freq. reference (0—f
max
) Freq. reference (0—f
max
)
3
Motor speed (0—Motor nomi-
nal speed)
Motor speed (0—Motor nominal
speed)
Motor speed (0—Motor nominal
speed)
4 Output current (0-I
nMotor
) Output current (0-I
nMotor
) Output current (0-I
nMotor
)
5 Motor torque (0—T
nMotor
) Motor torque (0—T
nMotor
) Motor torque (0—T
nMotor
)
6 Motor power (0—P
nMotor
) Motor power (0—P
nMotor
) Motor power (0—P
nMotor
)
7 Motor voltage (0-U
nMotor
) Motor voltage (0-U
nMotor
) Motor voltage (0-U
nMotor
)
8 DC-link volt (0—1000V) DC-link volt (0—1000V) DC-link volt (0—1000V)
9 PID controller ref. value AI1
10 PID contr. act. value 1 AI2
11 PID contr. act. value 2 Output freq. (f
min
- f
max
)
12 PID contr. error value Motor torque (–2…+2xT
Nmot
)
13 PID controller output Motor power (–2…+2xT
Nmot
)
14 PT100 temperature PT100 temperature
15
FB analogue output Process-
Data4 (NXS)
308 ANALOGUE OUTPUT FILTER TIME 234567 (2.3.3, 2.3.5.3, 2.3.3.3)
Defines the filtering time of the analogue output signal.
Setting this parameter value 0 will deactivate filtering.
PARAMETER DESCRIPTIONS VACON · 257
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM