3. Installation
3.1 Selecting Location
When mounting duct model transmitters:
Avoid installing in a location where condensation may fall on the sensor inside the duct.
Position the sensor in the center of the duct.
Select a site where the transmitter can be installed horizontally, onto the side of the duct.
Do not point the probe downward, as this will make condensation run down to the sensor.
When mounting wall model transmitters:
Select a location that represents well the area of interest.
Do not install on the ceiling.
Avoid placing the transmitter near heat and moisture sources, close to the discharge of
the supply air ducts, and in direct sunlight.
When mounting outdoor transmitters:
Install in a location with a good airflow around the transmitter.
Avoid placing the transmitter near windows, air conditioning units, or other heat and
moisture sources such as cooling towers.
Install the transmitter at least 2.5 m above ground level.
3.2
 HMD110/112 Installation
Medium size crosshead screwdriver (Pozidriv) for screws on cover and flange
Small slotted screwdriver for screw terminals
Drill with 2.5 mm and 13 mm bits for making the installation holes
Tools for cutting and stripping wires
19 mm open-end wrench for tightening the cable gland