A.4.4 Test value registers
Read the known test values from the test registers to verify the functionality of your Modbus
implementation.
Table 23 Modbus test registers (read-only)
Register
number
Register
address
Register description Data
format
Test value
7937 1F00
hex
Signed integer test 16-bit
integer
-12345
7938 1F01
hex
Floating point test 32-bit
float
-123.45
1F02
hex
7940 1F03
hex
Text string test text Text string "-123.45"
1F04
hex
1F05
hex
1F06
hex
A.5 Device identification objects
Table 24 Device identification objects
Object ID Object ID
(hexadecimal)
Object name Example contents
0 00
hex
VendorName "Vaisala"
1 01
hex
ProductCode "HMM170"
2 02
hex
MajorMinorVersion "1.2.3"
Software version of the device.
3 03
hex
VendorUrl "http://www.vaisala.com/"
4 04
hex
ProductName "Vaisala HUMICAP(R) Humidity and
Temperature Module HMM170"
5 05
hex
ModelName "7E2A2A0A000"
Configuration code of the device. Length
and content of the code are model-
specific.
6 06
hex
UserApplicationName User definable information text (see
configuration register 0A00
hex
)
HMM170 User Guide M212259EN-D