Appendix A _________________________________________________________ BACnet Reference
VAISALA ________________________________________________________________________ 87
Relative Humidity Object
This Analog Input Object exists only in the HMW95 model.
Table 19 Relative Humidity Object Properties
(Application Type)
(Conformance
Object Type = 0,
BACnetObjectType
(ENUMERATED)
BACnetEngineeringUnits
(ENUMERATED)
29 (percent-relative-
humidity)
BACnet Status Flags (BIT
STRING)
BACnet Reliability
(ENUMERATED)
BACnetEventState
(ENUMERATED)
NaN (COV reporting
disabled)
0.0 (same as limit for
UNDER_RANGE)
100 (same as limit for
OVER_RANGE)
Table 20 Status Flags
Event State equals 0 (NORMAL)
Reliability equals 0 (NO FAULT DETECTED)
Present Value may NOT be written via BACnet
Present Value may be written via BACnet
Table 21 Reliability
No contact to measurement module
Table 22 Event State
Reliability equals 0 (NO FAULT DETECTED)