EasyManua.ls Logo

Vaisala Optimus OPT100 - Uninstalling the DGA Monitor

Vaisala Optimus OPT100
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.10 Configuring Modbus protocol
Figure 35 Modbus settings page
1. In the user interface, select Settings > Network > Modbus.
2. Select the connection type(s) for which Modbus protocol should be enabled. Select TCP
(Ethernet), RTU (serial line), or both.
3. If you enabled Modbus RTU, configure the serial connection:
a. Select Baud rate for the connection. Available options are:
4800
9600
19200
38400
57600
115200
b. Select Transmission mode, 8E1 or 8N2.
c. Enter the Modbus Slave ID for the DGA monitor. Range 1 ... 247.
4. Click Apply to save your changes.
OPT100 Installation Guide M211857EN-R
76

Table of Contents

Other manuals for Vaisala Optimus OPT100