4. If you selected Serial port as the connection type, configure the following settings:
Baud rate
Baud rate of the serial connection. Available options are 4800, 9600, 19200, 38400,
57600, and 115200.
Transmission mode
Number of data bits, parity, and number of stop bits used in serial communication.
Available options are 8E1 and 8N2.
5. Set the classes used for the Gas alarm, Gas caution, and Device status events.
6. Select Apply to save your changes.
Select Download to download the DGA monitor device profile in XML format. It is
needed to configure your DNP3 master system.
5.12 Configuring IEC 61850 protocol
Figure 37 IEC 61850 settings page
IEC 61850 protocol is an optional feature and requires a license. If a license is not
installed on the DGA monitor, you cannot enable the protocol. Contact Vaisala for
acquiring the license.
OPT100 Installation Guide M211857EN-R
78