Threshold Value Settings
Click “Threshold value” in the category bar, to change to the threshold settings shown below.
The picture above are have the following settings:
Current warning value 5A: When the total current exceeds 5A, the buzzer sends out "beep, beep"
as an acoustical sound alarm.
Current overload value 6A: When the total current exceeds 6A, the PDU will cut off the power
supply of all output ports.
Warning voltage 250V: When the input voltage exceeds 250V, the buzzer sends out "beep, beep"
as an acoustical sound alarm.
Current overload value 300V: When the input voltage exceeds 300V, the PDU will cut off the
power supply of all output ports.
Temperature is under 5, or exceeds 40: When the built-in temperature and sensor is sensing,
that the environment temperature is under 5 or exceeds 40, the buzzer sends out "beep,
beep" as an acoustical sound alarm
Humidity warning value 80%: When the built-in humidity sensor is sensing, that the environment
humidity is more than 80%, the buzzer sends out "beep, beep" as an acoustical sound alarm.