Series 612 INSTALLATION
605262EE Edition 2018-08-20 73/
116
4.10.1.2 Manufactor specific Object Entries – Parameter data
The following VAT specific objects (valve parameter data) are available.
Index Object Name Sub-
Index
Description Type Valid Range Access Description
20E6h
SENSOR
OPERATION
MODE
00h Current
SENSOR
OPERATIO
N MODE
UINT8 0..4 RW
0 = no sensor
1 = 1 sensor
operation (sensor 1
input)
2 = 2 sensor
operation (low
range = sensor 2
input, high range =
sensor 1 input)
3 = 1 sensor
operation (sensor 2
input)
4 = 2 sensor
operation (low
range = sensor 1
input, high range =
sensor 2 input)
Refer to chapter:
«Valve and sensor
configuration»
20E7h
SENSOR FULL
SCALE RATIO
00h Current
SENSOR
FULL
SCALE
RATIO
FLOAT
32
1.0..100.0 RW Refer to chapter:
«Valve and sensor
configuration»
2118h
MAXIMUM
LEARN
PRESSURE
00h Max. learn
pressure
in ‰ of the
internal
pressure
upper scale
value
(1’000’000)
UINT16 0…1000 RW The pressure range
settings (see
chapter «EtherCAT
configuration» - 2.
Range of pressure
and position values)
does not influence
that parameter. The
«MAXIMUM LEARN
PRESSURE» is
always related to
the constant internal
upper scale value of
1’000’000.