Series 612
INSTALLATION
601894EA
Edition 2013-04-12
47/83
Setup function
Command
Acknowledgement
(within 10ms after reception of command)
Description
RANGE
CONFIGURATION
Set
[s:21][abcdefgh][CR][LF]
[s:21][CR][LF]
Get
[i:21][CR][LF]
[i:21][abcdefgh][CR][LF]
data length 8 characters
a range for POSITION: 0 = 0 1’000, 1 = 0 10’000, 2 = 0 100’000
bcdefgh upper value for PRESSURE and SENSOR READING: 1000 ... 1000000
e.g. 0010000 -> pressure range 0 10’000
This function defines the communication range between the valve and the host computer
for POSITION, PRESSURE and SENSOR READING.
Note: In case ZERO has been performed, gauge offset for PRESSURE and SENSOR
READING is compensated.
Note: In case 2 sensor operation for pressure control is selected, PRESSURE covers high
range gauge because switchover between sensors is done automatically.
SENSOR 1 READING and SENSOR 2 READING always return full scale values
according to selected range.
Above picture shows a 2 sensor system. In this configuration sensor 2 covers low range (100 mTorr) and sensor 1
covers high range (1 Torr). RANGE CONFIGURATION for PRESSURE resp. SENSOR READING is set to 10’000.
Switchover between sensors is done automatically.
0-10V
High range
sensor
Low range
sensor
0-10V
SENSOR 1 READING
0 10’000
100 mTorr
1 Torr
0 mTorr
SENSOR 2 READING
0 10’000
PRESSURE
0 10’000