EasyManua.ls Logo

VAT 650 Series - Page 63

VAT 650 Series
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4“ - 10”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
280672EB
2010-12-15
63/94
Signal
Type
Name
Start
Word
Byte
Length
Data Type
Valid
Range
Description
Signal
CLUSTER VALVE
FREEZE ADDRESS
SETPOINT
18 1 unsigned integer 0..254
Select a valve that should be frozen.
0 : master
1.. 254 : slave
Note: Only valid if bit FREEZE DATA
VALID is set
Bitmap
CLUSTER VALVE
FREEZE CONTROL
SETPOINT
19 1 boolean array
See bitmap table below
Signal
CLUSTER VALVE
MONITORING ADDRESS
SETPOINT
20 1 unsigned integer 0..254
Select a valve that should be
monitored.
0 : master
1..254 : slave
1) To adjust range refer to chapter: «Range of pressure and position values»
GENERAL CONTROL SETPOINT bitmap table:
Bit Description
0 ZERO
0 = No Operation
1 = ZERO adjust, the actual pressure signal is set to internal pressure 0. The valid range for
adjustment is limited to -1.4V…+1.4! Otherwise the sensor must be adjusted!
1
NOT USED (reserved)
-
2 PING PONG TX BIT
PING PONG TX BIT transmitted from the master (PLC), is used to check the loop "master PLC -
VAT station". See chapter: 3.11.9
Communication and timing control between Master
(PLC) and Station (Valve)
3
NOT USED (reserved)
-
4
ACCESS MODE LOCKED
Note: Access mode switching, only in remote mode possible (Host PLC).
Start mode Access mode locked bit End mode
local Set bit: 0Æ1 locked
locked Reset bit: 1Æ0 remote
remote Set bit: 0Æ1 locked
5-7
NOT USED (reserved)
-

Table of Contents

Related product manuals