EasyManua.ls Logo

VAT 650 Series - Page 64

VAT 650 Series
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4“ - 10”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
280672EB
2010-12-15
64/94
CLUSTER VALVE FREEZE CONTROL SETPOINT bitmap table:
Bit Description
0
FREEZE CONTROL
0 = Chosen cluster valve will become unfrozen
1 = Chosen cluster valve will become frozen
Note: Only valid if bit FREEZE DATA VALID is set.
1
FREEZE CONTROL
MODE
0 = Chosen cluster valve is in control mode position
1 = Chosen cluster valve is in control mode close
Note: Only valid if bit FREEZE DATA VALID is set.
2
FREEZE DATA VALID
Corresponds to
Signal CLUSTER VALVE FREEZE ADDRESS SETPOINT
Bit FREEZE CONTROL
Bit FREEZE CONTROL MODE
Signal CLUSTER VALVE FREEZE POSITION SETPOINT
0 = Data above are not valid and will not have an effect on the valve
1 = Data above are valid and will have an effect on the valve
3-7
NOT USED (reserved)
-
Note:
Valve will not accept freeze command when:
1. Digital input is active
2. Valve not yet synchronized
As soon as a valve is unfrozen, the valve starts to follow the Master valves plate position, meaning the plate might
move immediately.
Example for individual valve control (freeze mode):
Task: Freeze the valve with address 3 and set the position to open position
1. Set signal CLUSTER VALVE FREEZE ADDRESS SETPOINT = 3
2. Set bit FREEZE CONTROL MODE = 0 (control mode position)
3. Set bit CLUSTER VALVE FREEZE POSITION SETPOINT = max position (default 100’000)
4. Set bit FREEZE CONTROL = 1 (enable freeze mode for this cluster valve)
5. Activate the values by setting the following bit: Set bit FREEZE DATA VALID
Example for individual valve monitoring:
Task: Select the cluster valve with address 3 to monitor
1. Set signal CLUSTER VALVE MONITORING ADDRESS SETPOINT = 3 in «OUTPUT buffer»
2. Wait until the signal CLUSTER VALVE MONITORING ADDRESS in «INPUT Buffer» is = 3. Now the individual
information for the cluster valve with address 3 are available:
CLUSTER VALVE POSITION
CLUSTER VALVE CONTROL MODE
CLUSTER VALVE STATUS

Table of Contents

Related product manuals