Displayed Alarm Messages
2
Displayed Alarm Messages
Common Alarm messages and a possible cause/action for the Alarms are listed in the table below. Actual Alarms
displayed by a particular console will depend upon the features installed.
Short Device IDs used in the table below:
C = 2-wire CL sensor Co = Comm device G = Groundwater sensor
H = 3-wire CL sensor I = External input L = Liquid sensor
MS = Mag sensor P = Printer Pm = Pump
Q = PLLD line R = Relay
(TLS4/TLS-450PLUS), R = Receiver (TLS-3XX)
T = Tank s = Smart sensor V = Vapor sensor
Message
Short
Device ID Cause Action
Annual Test Needed Alarm Q, T System failed to perform an annual test (0.1 gph
[0.38 lph]) in the programmed number of days.
Schedule a 0.1 gph (0.38 lph) test.
Annual Test Needed Warn-
ing
Q, T System failed to perform an annual test (0.1 gph
[0.38 lph]) in the programmed number of days.
Schedule a 0.1 gph (0.38 lph) test.
Annual Line Test Fail
Alarm
Q 0.1 gph (0.38 lph) line test failure. Dispensing
halts, if programmed to do so.
Consult PLLD Alarm Quick Help Guide and
PLLD diagnostic screens.
Annual Leak Test Fail
Alarm
T System failed an annual in-tank leak test. Rerun in-tank leak test. If second test fails,
call for service.
Autodial Failed Alarm
(TLS4/TLS-450PLUS only)
Co System failed to connect to a remote receiver
after ‘n’ tries.
Verify the address book settings for the con-
tact are correct (i.e., modem device number,
phone number to dial), verify the receiving
device (fax or modem) is operational. Con-
tact technical support for assistance.
Cold Temperature Warning T Probe temperature drops below -4°F (-20°C). Probe returns to normal operation after
probe temperature rises above 0°F
(-17.8°C).
Continuous Handle On
Alarm
Q Handle signal has been active for a programmed
number of hours.
Call for service following the procedures
established for your site.
CSLD Rate Increase Warn-
ing
T An excessive amount of fluid leaked into the tank
during a test period.
Call for service following the procedures
established for your site.
Density Offset Warning T The console calculated density offset amount
exceeds the threshold amount:
10.012 kg/m
3
(
0.625 lbs/ft
3
).
Check the density offset values configured
for the probe. If these values are correct, the
probe float may be contaminated, and
should be replaced.
NOTE: This alarm message will continue to
display (scroll) in the System Status box
until you correct the cause of the problem.
Density Warning T Tank density is either:
• Greater than the tank density low limit plus
1.00kg/m
3
(0.062 lbs/ft
3
)
• Or is less than the tank density high limit minus
1.00 kg/m
3
(0.062 lbs/ft
3
)
Verify fluid density (retest when product
density is within the tank density low and
high limits.
Delivery Needed Warning T Product level dropped below programmed limit. Call for a delivery.

Other manuals for Veeder-Root TLS-3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-3 Series and is the answer not in the manual?

Veeder-Root TLS-3 Series Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-3 Series
CategoryMusic Mixer
LanguageEnglish

Related product manuals