Maintenance and Diagnostics
Maintenance and Diagnostics
The transmitter system alerts you to detector problems by:
Posting messages on the Ohmview 2000 message screen.
De-energizing the output relay.
Distinctly changing the current loop output.
Tracking the current status and history in the Gauge status screens.
Alarm Types
Name
Diagnostic
when periodic procedures are due.
Analog
(0) counts.
If analog alarm is on, check the following:
Is source holder shutter in On or Open position to create the required radiation
field?
Is there extreme build-up on walls or other material that is shielding detector
from radiation field?
Are electrical connections from sensor assembly to CPU board damaged or
disconnected?
Process
low limit).
Enter choice of low or high limit and set point on Alarm | Relay Setup tab. This
alarm only works for output relay.
The gauge acknowledges or resets process alarm when process value returns to set
point value.
X-ray
radiation field. This change prevents control problems when external radiographic
sources are in the area during vessel inspections. Gauge sets current loop output at
value measured 10 seconds before condition. Gauge cycles until radiation field is
back to normal level or until a time-out period of 60 minutes passes.