Capacitive electrodes EL 4 … 20 mA - compact 37
Connection to a VEGA-signal conditioning
instrument
(fig. 3, page 38)
When you operate a sensor suitable for HART
®
on a VEGA-signal conditioning instrument, you
have to provide the sensor connection on the
signal conditioning instrument with a resistor of
the following table for the duration of the
HART
®
-adjustment.
VEGA-signal conditioning Rx
instrument
VEGAMET 513, 514, 515, 602
VEGATRENN 544
VEGATOR 521…527 50 … 100 Ω
VEGAMET 614 no additional
VEGADIS 371 resistor
required
VEGAMET 601 200 … 250 Ω
VEGASEL 643 150 … 200 Ω
VEGAMET 513 S4, 514 S4
515 S4 100 … 150 Ω