11
5 Set up with the display and adjustment module
VEGADIF 85 • Probus PA
53575-EN-230814
1 2
Fig. 6: Installing the display and adjustment module in the double chamber
housing
1 In the electronics compartment
2 In the connection compartment
Note:
If you intend to retrot the instrument with a display and adjustment
module for continuous measured value indication, a higher lid with an
inspection glass is required.
5.2 Parameter adjustment - Quick setup
To quickly and easily adapt the sensor to the application, select the
menu item " Quick setup" in the start graphic on the display and
adjustment module.
Carry out the following steps in the below sequence.
You can nd " Extended adjustment" in the operating instructions
VEGADIF 85.
Instrument address
In the rst menu item you have to enter an address for the instrument
on the bus. The selection switches on the electronics module are
preset to address 126. This means that the address can be changed
via the display and adjustment module.
Measurement loop name
In this menu item you assign a suitable measurement loop name.
Permitted are names with a maximum of 19 characters.
Quick setup - Presettings