23
5 Connecting to power supply
VEGAFLEX 81 • Modbus and Levelmaster protocol
42283-EN-140430
5.5 Supplementary electronics
You can use the supplementary electronics - additional current output
to provided a second measured value.
Both current outputs are passive and need a power supply.
1
2
+
( )
(-)
I
4...20mA
I I
4...20mA
7
8
+
( )
(-)
3
1 2
Fig.15:Connectioncompartmentdoublechamberhousing,supplementary
electronics - additional current output
1 Firstcurrentoutput(I)-Voltagesupplyandsignaloutput(HART)
2 Secondcurrentoutput(II)-Voltagesupplyandsignaloutput(withoutHART)
3 Groundterminalforconnectionofthecablescreen
The radio module PLICSMOBILE is an external GSM/GPRS radio
unit for transmission of measured values and for remote parameter
adjustment.
1
USB
Status
Te st
SIM-Card
1
2
+
( )
(-)
Fig.16:RadiomodulePLICSMOBILEintegratedintheconnectioncompart-
ment
1 Voltage supply
Youcannddetailedinformationonconnectioninthesupplementary
instructions "PLICSMOBILEGSM/GPRSradiomodule".
5.6 Switch-on phase
After connecting the instrument to power supply or after a voltage
recurrence, the instrument carries out a self-check for approx. 30 s:
•
Internal check of the electronics
•
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
Supplementary electron-
ics - Additional current
output
Supplementary elec-
tronics - Radio module
PLICSMOBILE