8 Diagnostics and service
VEGAFLEX 81 • Modbus and Levelmaster protocol
42283-EN-140430
Measurement error during emptying
Fault description Error pattern Cause Rectication
7. Measured value re-
mains unchanged in
the close range during
emptying
Level
time
0
False echo larger than the level
echo
Level echo too small
Eliminate false signals in the
close range
Remove contamination on the
probe. After having removed
the source of the false signals,
the false signal suppression
must be deleted.
Carry out a new false signal
suppression
8. Measured value re-
mains reproducible
in one position during
emptying
Level
time
0
Stored false signals in this
position are larger than the
level echo
Delete false signal memory
Carry out a new false signal
suppression
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven
days a week around the clock.
Sinceweoerthisserviceworldwide,thesupportisprovidedin
English. The service itself is free of charge, the only costs involved are
the normal call charges.
8.5 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with ap-
propriate Ex approval may be used.
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electron-
icsmodulesareadaptedtotherespectivesensoranddierinsignal
output or voltage supply.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
In the factory
Or on site by the user
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside
of the housing as well as on the delivery note.
Whenloadingonsite,rstofalltheorderdatamustbedownloaded
from the Internet (see operating instructions manual "Electronics
module").
Reaction after fault recti-
cation
24 hour service hotline