6 Set up with the display and adjustment module
VEGAFLEX 86 • Probus PA
44232-EN-160518
6.3 Parameter adjustment - Quick setup
To quickly and easily adapt the sensor to the application, select
the menu item "Quick setup" in the start graphic on the display and
adjustment module.
The following steps for the quick setup can be reached also in the
"Extended adjustment".
Instrument address
Measurement loop name
Medium type (optional)
Application
Max. adjustment
Min. adjustment
False signal suppression
You can nd the description of the individual menu items in the follow-
ing chapter "
Parameteradjustment-Extendedadjustment".
6.4 Parameter adjustment - Extended adjustment
For technically demanding measuring points, you can carry out
extended settings in "Extendedadjustment".
The main menu is divided into ve sections with the following func-
tions:
Setup: Settings, e.g. measurement loop name, medium, application,
vessel, adjustment, AI FB 1 Channel - Scaling - Damping, device
units, false signal suppression, linearization
Display: Language setting, settings for the measured value indication
as well as lighting
Diagnosis: Information, for example on the instrument status, pointer,
reliability, AI FB 1 simulation, echo curve
Additional adjustments: Sensor address, PIN, date/time, reset,
copy sensor data
Quick setup
Main menu