9 Diagnostics and servicing
VEGAFLEX 86 • Probus PA
44232-EN-160518
Information:
Please maintain the specied torque so that the max. tensile strength
of the connection remains.
6. Enter new probe length and if necessary the new probe type and
then carry out a fresh adjustment (see "Setupprocedure,Carry-
ingoutmin.adjustment-Carryingoutmax.adjustment").
The rod or cable of the probe can be shortened individually.
1. Mark the requested length with mounted measuring rod.
2. Cable: Loosen the pins on the gravity weight (hexagon 3)
3. Cable: remove the pins
4. Cable: Pull the cable out of the gravity weight
5. Shorten the cable/rod with a cut-o wheel or metal saw at the
marking. Take note of the specications in the following illustration
when shortening the cable.
6. Cable with gravity weight: Shift the cable according to the drawing
into the gravity weight
7. Cable with gravity weight: Fasten cable with the pins, torque 7 Nm
(5.16 lbf ft)
Cable with centering weight: Fasten cable with the pins, torque
7 Nm (5.16 lbf ft) and x the clamping part on the centering
weight.
8. Enter new probe length and then carry out a fresh adjustment
(see "Setupprocedure,Carryingoutmin.adjustment-Carrying
out max. adjustment").
1
1
1
2 2 3
A
B
C
45 mm
(1.77")
100 mm
(3.94")
25 mm
(0.98")
50 mm
(1.97")
Fig. 52: Shortening the cable probe
A Gravityweight-cableø4mm
B Gravityweight-cableø2mm
C Centeringweight-cableø2mm
1 Threadedpins
2 ThreadM8foreye-bolt
3 Fixing screw - centering weight
Shorten cable/rod