5
VEGAMET 141, 142
63696-EN-201216
The sta must be trained in explosion protection
The sta must be familiar with the respectively valid regulations, e.g. planning and installation
acc. to IEC 60079-14
Make sure when working on the instrument (mounting, installation, maintenance) that there is no
explosive atmosphere present, the supply circuits should be voltage-free, if possible.
The instrument has to be mounted according to the manufacturer specications, the Certicate
of Conformity and the valid regulations and standards
Modications on the instrument can inuence the explosion protection and hence the safety,
therefore repairs are not permitted to be conducted by the end user
Modications must only be carried out by employees authorized by VEGA company
Use only approved spare parts
Components for installation and connection not included in the approval documents are only
permitted if these correspond technically to the latest standard mentioned on the cover sheet.
They must be suitable for the application conditions and have a separate certicate. The special
conditions of the components must be noted and if necessary, the components must be inte-
grated in the type test. This applies also to the components already mentioned in the technical
description.
Mounting
Keep in mind for instrument mounting
Mechanical damage on the instrument must be avoided
Mechanical friction must be avoided
Maintenance
To ensure the functionality of the device, periodic visual inspection is recommended for:
Secure mounting
No mechanical damages or corrosion
Worn or otherwise damaged cables
No loose connections of the line connections, equipotential bonding connections
Correct and clearly marked cable connections
Intrinsic safety "i"
Observe the valid regulations for the interconnection of intrinsically safe circuits.
The instrument is only suitable for connection to certied, intrinsically safe instruments
If the intrinsically safe circuit is lead into dust-explosive areas of zone 20 or 21, please make
sure that the instruments which are connected to these circuits meet the requirements of
EPL Da or EPL Db and are certied respectively
8 Electricaldata
VEGAMET 141, 142
Non-intrinsicallysafecircuit
Supplycircuit:
Terminals 91[+, L], 92[-, N] U = 24 … 65 V DC (-15 … +10 %)
P = 3 W (VEGAMET 141), 4 W (VEGAMET 142)
U = 100 … 230 V AC (-15 … +10 %), 50/60 Hz
P = 10 VA (VEGAMET 141), 12 VA (VEGAMET 142)
U
m
= 253 V AC