18
7 Set up with the integrated display and adjustment unit
VEGAMET 341 • 4 … 20 mA
63730-EN-210616
Turn/Push button Function
Short pressure Entry to the menu level
Jump to selected menu item
Edit parameter
Select editing position
Save value
Turn Change between the measured value indications
Navigation in the menu items
Change parameter values
Long pressure Jump to next higher menu
Key pressing longer than 2 s, direct return to the
measured value indication
Cancel input without saving
Approx. 60 minutes after the last pressing of a key, an automatic reset
tomeasuredvalueindicationistriggered.Anyvaluesnotconrmed
will not be saved.
7.2 Measured value and menu item display
The measured value display shows the digital display value, the
measuring loop name (measuring loop TAG) and the unit. In addition,
an analogue bar graph can be displayed. Up to three measured value
indicationswithamaximumthreedierentmeasuredvaluescanbe
congured.Ifpumpcontrolisactivated,anadditionalstatusbarwith
display of the assigned pumps is available.
Measured values are displayed according to the following presenta-
tion:
1
2
3
4
5
6
7
TAG-No. 1
%
47.8
1
2
Fig. 8: Example measured value indication (measured value with bargraph)
1 Measurement loop name
2 Measured value
3 Unit
4 Status message acc. to NAMUR NE 107
5 Status bar for pump control
6 Bargraph measured value
7 Active measured value indication
The display is equipped with a background lighting for better visibility.
It serves simultaneously as a status display which is also visible from
Functions turn/push
button
Time functions
Measured value indica-
tion
Status display/back-
ground lighting