EasyManua.ls Logo

Vega VEGAMET 391 - Example; Setup

Vega VEGAMET 391
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Probable failures of the pumps can be processed in addition via the
digital inputs.
With this pump control, there are two dierent versions:
l Pump control 1: The upper switching point determines the switch-
o point for the relay, whereas the lower switching point
determines the switch-on point
l Pump control 2: The upper switching point determines the switch-
on point for the relay, whereas the lower switching point
determines the switch-o point
Two pumps should empty the vessel when a certain level is reached.
At 80 % lling, the pump with the shortest running time should switch
on. If the level nevertheless increases, a second pump should switch
on at 90 %. Both pumps should switch o again at 10 % lling.
Select in the DTM navigation section the menu items "Meas. loop -
Outputs - Relay".
l Set mode "Pump control 2" for relay 1 and 2.
l Enter the switching points for the concerned relays as follows:
- Relay 1 upper switching point = 80.0 %
- Relay 1 lower switching point = 10.0 %
- Relay 2 upper switching point = 90.0 %
- Relay 2 lower switching point = 10.0 %
The function of pump control 2 is shown in detail in the following
diagram. The previously described example is used as a basis.
Rel. 1: 80% On
On
Off
Off
On
Rel. 2: 90% On
Rel. 1, 2: 10% Off
10 30 20 20 15
t [h]
5
Rel. 1
Rel. 2
Fig. 12: Example of a pump control 2
With a pump control, there is also the option of switching on pump
monitoring. For this, a return signal on the respective digital input is
required. The as signment of the digital inputs to the relais is preset:
l Digital input 1 - Relay 1
l Digital input 2 - Relay 2
l Digital input 3 - Relay 3
Example
Setup
VEGAMET 391 4 20 mA/HART signal conditioning instrument 43
8 Application examples
36032-EN-091116