45
10Measuredvalue/Statusles
RS232/Ethernet connection • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30325-EN-130701
10 Measuredvalue/Statusles
10.1 Descriptionofthemeasurementdatales
ThePC/DCSvaluescanbesentinfourdierentleformatsfrom
theinstrumentviae-mailorretrievedviahttp.Enterthefollowing
line into your browser: http://ip-address or Host name/le name,e.g.
http://192.168.200.200/val.htm.
Theleshavethefollowingname:
•
val.txt(textle)
•
val.csv(CSVle)
•
val.htm(HTMLle)
•
val.xml(XMLle)
Thecontentsofthelesconsistsofaheaderwiththefollowinginfor-
mation:
•
#System: VEGAMET 625(instrumenttype)
•
#Version: 1.91(Firmwareversion)
•
#TAG: Device Name(device-TAG)
•
#SNR: 11162431(instrumentserialnumber)
•
#Date: 25.10.04(transmissiondate)
•
#Time: 10:26:58(transmissiontime)
•
#Ontime: 02:58:51(switchonperiod)
ThePC/DCSvaluesaretransmittedwiththefollowinginformation:
001,"TAG-No. 1",98.75,%
•
001(PC/DCSnumber)
•
TAG-No(measurementloopTAG)
•
98.75(measuredvalue)
•
%(unit)
AnentryexistsintheleforeachPC/DCSoutputassignedinVE-
GAMET/VEGASCAN/PLICSRADIO.FortheswitchinginputsofPLIC-
SRADIOC62(measurementloops4…6)thevalues0.00(switch
open)and100.00(switchclosed)aretransmittedasmeasured
values,theunitisdeleted.
WithaTXTle,informationistransmittedastext.
Exampleofthecontentofa"val.txt"leofaVEGAMET625.
File content Description
#System:VEGAMET625 Instrument type
#Version:1.91 Firmwareversion
#TAG:DeviceName Device-TAG
#SNR:11162431 Instrumentserialnumber
#Date:25.10.04 Transmissiondate
#Time:10:26:58 Transmissiontime
#Ontime:02:58:51 Switch on period
#PLS;TAG;VALUE;UNIT Headingmeasuredvalues
Conguration
TXTle