48
10Measuredvalue/Statusles
RS232/Ethernet connection • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62
30325-EN-130701
<device>
Informationwithinthe"<device>"-TAGisinformationaboutthesignal
conditioninginstrument.Itisstatedonceatthebeginningofthedocu-
ment.
<dataitem>
"<dataitem>"-TAG thereismeasuredvalueinformationfromaPC/
DCSoutput.ForeachassignedPC/DCSoutputthereexistssucha
TAG,i.e.uptosixoftheseTAGscanexistwithaVEGAMET/PLICS-
RADIO,upto30withaVEGASCAN.
10.2 Descriptionofthestatusles
Inadditiontothemeasuredvaluelethereisalsoastatuslewith
status,relayandcurrentoutputinformation.Forretrievalviahttp,enter
thefollowinglineintoyourbrowser:http://ip-address or Host name/le
name,e.g.http://192.168.200.200/state.htm.
Theleshavethefollowingname:
•
state.txt(textle)
•
state.csv(CSVle)
•
state.htm(HTMLle)
•
state.xml(XMLle)
Thecontentsofthelesconsistsofaheaderwiththefollowinginfor-
mation:
•
#System: VEGAMET 625(instrumenttype)
•
#Version: 1.91(Firmwareversion)
•
#TAG: Device Name(device-TAG)
•
#SNR: 11162431(instrumentserialnumber)
•
#Date: 25.10.04(transmissiondate)
•
#Time: 10:26:58(transmissiontime)
•
#Ontime: 02:58:51(switchonperiod)
•
#Fault relay: 0(statusfailsaferelay)
Thereisstatusinformationforeachmeasurementloop.Itincludesda-
taonthecurrentdevicestatus,incl.thevaluesorswitchingconditions
ofthecurrentandrelayoutputsofVEGAMET/PLICSRADIOC62.
WithaTXTle,informationistransmittedastext.
Exampleofthecontentofa"state.txt"leofaVEGAMET625.
File content Description
#System:VEGAMET625 Instrument type
#Version:1.91 Softwareversion
#TAG:DeviceName Device-TAG
#SNR:11162431 Instrumentserialnumber
#Date:25.10.04 Transmissiondate
#Time:10:26:58 Transmissiontime
#Ontime:02:58:51 Switch on period
Conguration
TXTle