EasyManua.ls Logo

Vega VEGAMET 624 - Option TIME; Option REPEAT

Vega VEGAMET 624
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enquiry:
$001-003
Answer:
=001# 67.3 # kg
=002# 824.3 #%
=003#-67.3 #m
2.10 Option TIME
By adding the attribute TIME, the current time will be
transmitted before the answer. The transmission of date/time
information is carried out in the format "@YYYY/MM/DD
hh:mm:ss". The character string contains 21 characters incl.
CR.
l YYYY - year with 4 decimal places
l MM - month with 2 decimal places
l DD - day with 2 decimal places
l hh - hours in 24 h format with 2 decimal places
l mm - minutes with 2 decimal places
l ss - seconds with 2 decimal places
Note:
The character string is terminated with CR.
Enquiry:
$001 time
Answer:
@2005/04/07 09:00:50
=001# 24.44 #%
2.11 Option REPEAT x
By attaching the attribute REPEAT and a number x, the
transmitted enquiry will be repeated every x seconds. If the
value for the repetition is = 0, a measured value is only
retrieved once. A repetition rate less than 5 seconds is not
possible.
Enquiry: (activate autom. repetition every 10 sec.)
$001 time repeat 10
Answer:
@2005/04/07 09:02:19
=001# 27.55 #%
@2005/04/07 09:02:29
=001# 27.77 #%
Example:
Example
Example:
Modbus-TCP, VEGA ASCII protocol - VEGAMET 624/625, VEGASCAN 693, PLICSRADIO 35
VEGA ASCII protocol
30768-EN-070730