@2005/04/07 09:02:39
=001# 28.44 #%
Enquiry: (terminates the repetition)
$001 time repeat 0
2.12 Option STORE
By adding the attribute STORE, the enquiry is stored in the
EEPROM memory up to the option STORE. After switching on
the instrument again, this enquiry will be used as input
telegram and an answer will be generated.
Note:
This option is only available for the RS232 interface.
Enquiry:
% time repeat 10 store
Answer:
@2005/04/07 09:02:19
=001# 27.55 %
=002# 28.44%
@2005/04/07 09:02:29
=001# 27.55 %
=002# 28.44%
Voltage interruption: If the instrument is switched o now and
then switched on again, the instrument sends automatically the
answer to the saved enquiry telegram.
@2005/04/07 09:03:19
=001# 27.55 %
=002# 28.44%
2.13 Option SUM
By attaching the attribute SUM, a check sum is built for each
line of the answer. T he check sum is the sum of all binary sign
up to the start of the sum itself Modulo 65535.
Enquiry:
%1sum
Answer:
=001# 27.55 %(00553)
Example
Example
36 Modbus-TCP, VEGA ASCII protocol - VEGAMET 624/625, VEGASCAN 693, PLICSRADIO
VEGA ASCII protocol
30768-EN-070730