7 Set up with the integrated display and adjustment unit
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
The characteristics of the current output can be set to 0 … 20 mA,
4 … 20 mA or inverted. The reaction in case of failure can also be
adapted to the requirements. The reference value you refer to can
also be selected.
7.4.2 Indication
Ameasuredvaluewindowcandisplayuptothreedierent,user-
congurablemeasuredvaluessimultaneously.Inaddition,uptothree
dierentmeasuredvaluewindowscanbedisplayed,whichcanbe
selected using the arrow keys. Alternatively, the display of the meas-
ured value windows can also be changed automatically at intervals of
approx. 3 seconds.
In the menu item "Display - Number of measured value windows"
youcancongurehowmanymeasuredvaluewindowsaretobe
displayed.
Thecontentofthemeasuredvaluewindowisconguredinthemenu
item "Display - Measured value window".Upto3dierentmeasured
values can be displayed in one window. For each measured value
itisalsopossibletocongurewhichdisplayvalue(percent,scaled,
sensor value, …) is displayed. In addition, the display format (number
ofdecimalpositions)canalsobecongured.Inaddition,abargraph
can be displayed parallel to the measured value (only available when
displaying a single measured value).
In the menu item "Display - Options - Brightness" the brightness of the
background lighting can be adjusted.
In the menu item "Display - Options - Contrast" the contrast of the
display can be adjusted.
In the menu item "Display - Options - Lighting" the lighting can be set
permanently to "Permanently ON" or "Automatically OFF" (after two
minutes). With the setting "Automatically OFF" the lighting is switched
on for two minutes as soon as any button is pressed.
In the menu item "Display - Menu language", the requested language
can be adjusted. The following languages are available:
•
German
•
English
•
French
•
Spanish
•
Italian
•
Dutch
7.4.3 Extended functions
Relay4canoptionallybeconguredasadditionaloperatingrelayor
as a fail safe relay. In this menu item, the fail safe relay can be activat-
edordeactivated.Ifrelay4istobeconguredasanoperatingrelay,it
must still be activated as an operating relay after deactivation as a fail
safe relay. This is done in menu item"Measuring point - Relay 4"
Number of measured
value windows
Measured value window
1 … 3
Options - Brightness
Options - Contrast
Options - Lighting
Menu language
Fail safe relay