54
12 Diagnostics and servicing
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
Error code Cause Rectication
S115
Pump control:
Faulty interfer-
ence behaviour
Several relays
are assignef to
the pump control
which are not set
to the same fail-
ure mode
All relays which are assigned to the
pump control must be set to the same
failure mode
S116
Pump control:
Operating mode
faulty
Several relays
that are not con-
guredwiththe
same mode are
assigned to the
pump control
All relays which are assigned to the
pump control must be set to the same
mode
Error code Cause Rectication
C029
Simulation
Simulation active Finish simulation
Error code Cause Rectication
M117
Pump signals
failure
Pump signals
failure
Check faulty pump
12.4 Software update
An update of the device software is possible via the Bluetooth inter-
face.
The following components are required:
Instrument
Voltage supply
PC/Notebook with PACTware/DTM
Currentinstrumentsoftwareasle
Youcanndthecurrentinstrumentsoftwareaswellasdetailedinfor-
mation on the procedure in the download area of our homepage.
Caution:
Instruments with approvals can be bound to certain software versions.
Thereforemakesurethattheapprovalisstilleectiveafterasoftware
update is carried out.
Youcannddetailedinformationinthedownloadareaonourhome-
page.
12.5 How to proceed if a repair is necessary
Youcanndaninstrumentreturnformaswellasdetailedinformation
about the procedure in the download area of our homepage. By doing
this you help us carry out the repair quickly and without having to call
back for needed information.