12 Diagnostics and servicing
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
Error code Cause Rectication
S115
Pump control:
Faulty interfer-
ence behaviour
Several relays
are assignef to
the pump control
which are not set
to the same fail-
ure mode
All relays which are assigned to the
pump control must be set to the same
failure mode
S116
Pump control:
Operating mode
faulty
Several relays
that are not con-
guredwiththe
same mode are
assigned to the
pump control
All relays which are assigned to the
pump control must be set to the same
mode
Error code Cause Rectication
C029
Simulation
Simulation active Finish simulation
Error code Cause Rectication
M117
Pump signals
failure
Pump signals
failure
Check faulty pump
12.4 Software update
An update of the device software is possible via the Bluetooth inter-
face.
The following components are required:
•
Instrument
•
Voltage supply
•
PC/Notebook with PACTware/DTM
•
Currentinstrumentsoftwareasle
Youcanndthecurrentinstrumentsoftwareaswellasdetailedinfor-
mation on the procedure in the download area of our homepage.
Caution:
Instruments with approvals can be bound to certain software versions.
Thereforemakesurethattheapprovalisstilleectiveafterasoftware
update is carried out.
Youcannddetailedinformationinthedownloadareaonourhome-
page.
12.5 How to proceed if a repair is necessary
Youcanndaninstrumentreturnformaswellasdetailedinformation
about the procedure in the download area of our homepage. By doing
this you help us carry out the repair quickly and without having to call
back for needed information.