10 Diagnostics and servicing
VEGAPULS 11 • Two-wire 4 … 20 mA
58350-EN-200806
Fault description Cause Rectication
Measured value jumps spo-
radically to 100 % during
lling
Level
0
Varying condensation or contamination
on the antenna
Carry out a false signal suppression
or increase false signal suppression
with condensation/contamination in the
close range by editing
Measured value jumps to
≥100%or0mdistance
Level
Level echo is no longer detected in
the close range due to foam genera-
tion or false signals in the close range.
Thesensorgoesintooverllprotection
mode. The max. level (0 m distance)
as well as the status message " Overll
protection" are output.
Check measuring point: Antenna should
protrude out of the threaded mounting
socket, possible false echoes through
angesocket?
Remove contamination on the antenna
Liquids: Measurement error during emptying
Fault description Cause Rectication
Measured value remains un-
changed in the close range
during emptying
Level
False signal larger than the level echo
Level echo too small
Check measuring point: Antenna should
protrude out of the threaded mounting
socket, possible false echoes through
angesocket?
Remove contamination on the antenna
In case of interferences due to instal-
lations in the close range: Change
polarisation direction
After eliminating the false signals, the
false signal suppression must be de-
leted. Carry out a new false signal
suppression
Measured value jumps spo-
radically towards 100 %
during emptying
Level
Varying condensation or contamination
on the antenna
Carry out false signal suppression or in-
crease false signal suppression in the
close range by editing
With bulk solids, use radar sensor with
purging air connection
Bulk solids: Measurement error at constant level
Fault description Cause Rectication
Measured value shows a too
low or too high level
Level
Min./max. adjustment not correct Adapt min./max. adjustment
Incorrect linearization curve Adapt linearization curve