44 VEGAPULS 51K … 54K
21750-EN-031222
with
medium
Min.
adjust
at %
XXX.X
Max.
adjust
at %
XXX.X
Signal
condit
ioning
Scal
ing
0 %
corres
ponds
XXXX
100 %
corres
ponds
XXXX
Deci-
mal
point
888.8
prop.
to
Mass
Unit
Kg
Adjustment with medium
Fill the vessel e.g. to 10 % and enter 10 % in
the menu "
Min. adjust
“ with the "
+
“ and "
keys. Then fill the vessel, e.g. to 80 % or
100 % and enter 80 % or 100 % in the menu
"
Max. adjust
“ with the "
+
“ and "
“ keys.
4. Conditioning
Under the menu item "
Conditioning
“, you
select product distance at 0 % and at 100 %
filling. Then, you enter the parameter and the
physical unit as well as the decimal point.
Enter in the menu window "
0 % corresponds
the numerical value of the 0 % filling. In the
example of the adjustment with the PC and
the adjustment software VVO, this would be
45 for 45 liters.
Confirm with "
OK
“.
With the "—>“ key you switch to the 100 %
menu. Enter here the numerical value of your
parameter corresponding to a 100 % filling.
In the example 1200 for 1200 liters.
With the "
+
“ or "
“ key you can
assign a level distance (exam-
ple 5.85 m) to the previously
adjusted percentage value. If
you do not know the distance,
you have to do a sounding.
The adjusted product dis-
tance is written in the sensor
and the display stops flash-
ing.
You thereby adjusted the lower product dis-
tance as well as the percentage filling value
corresponding to the lower product distance.
Note:
For level detection outside the operating range,
the operating range must be corrected accord-
ingly in the menu "
Sensor optimisation/Operat-
ing range“
.
OK
+
or
100.0%
at
m (d)
XX.XXX
(max. adjustment)
Now you make the max. adjustment (upper
product distance) (example: 100 % and
1.270 m product distance). First, enter the
percentage value and then the product dis-
tance corresponding to that percentage value.
Note:
The difference between the entered values of
the lower product distance and the upper
product distance should be as big as possi-
ble, preferably at 0 % and 100 %. If the val-
ues are very close together, e.g. lower
product distance at 40 % (3.102 m) and
upper product distance at 45 % (3.331 m),
the measurement will be less accurate. A
characteristic curve is generated from the
two points. Even the smallest deviations
between actual product distance and en-
tered product distance will considerably
influence the slope of the characteristic
curve. If the adjustment points are too close
together, small errors inflate to considerably
larger ones when the 0 % or the 100 % value
is outputted.