15
5 Set up with the display and adjustment module
VEGAPULS 61 • Probus PA
47106-EN-210621
The radar sensor measures the distance from the sensor to the
medium surface. For indication of the real level, an allocation of the
measured distance to the percentage height must be carried out.
100%
0%
0,5 m
(19.68
")
5 m
(196.9
")
2
1
3
Fig. 11: Parameterisation example, Min./max. adjustment
1 Min. level = max. measuring distance
2 Max. level = min. measuring distance
3 Reference plane
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
other distances, for example, 10 % and 90 % is also possible. Starting
point for these distance specications is always the seal surface of
the thread or ange.
The function " Echo curve memory" makes it possible to save the
echo curve at the time of setup. This is generally recommended, and
it is absolutely necessary if you want to use the Asset Management
functions. If possible, the curve should be saved with a low level in the
vessel.
With the adjustment software PACTware and a PC, a high resolution
echo curve can be displayed and used to recognize signal changes
during operation. In addition, the echo curve of setup can be dis-
played in the echo curve window and compared with the current echo
curve.
The following circumstances cause interfering reections and can
inuence the measurement:
High mounting nozzles
Vessel internals such as struts
Parameterization example
Diagnostics - Echo curve
memory
Additional settings - False
signal suppression