EasyManua.ls Logo

Vega VEGAPULS 61 - Asset Management Function

Vega VEGAPULS 61
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
8 Diagnosis, asset management and service
VEGAPULS 61 • Modbus and Levelmaster protocol
41717-EN-160224
Further echo curves: Up to 10 echo curves can be stored in a ring
buerinthismemorysection.Furtherechocurvesarestoredvia:
PC with PACTware/DTM
Control system with EDD
8.3 Asset Management function
The instrument features self-monitoring and diagnostics according to
NE 107 and VDI/VDE 2650. In addition to the status messages in the
following tables, detailed error messages are available under menu
item "Diagnostics" via the display and adjustment module, PACTware/
DTM and EDD.
The status messages are divided into the following categories:
Failure
Function check
Outofspecication
Maintenance requirement
and explained by pictographs:
41 2 3
Fig. 35: Pictographs of the status messages
1 Failure - red
2 Out of specication - yellow
3 Function check - orange
4 Maintenance - blue
Failure: Due to a malfunction in the instrument, a failure message is
outputted.
This status message is always active. It cannot be deactivated by the
user.
Function check: The instrument is in operation, the measured value
is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Outofspecication: The measured value is unstable because the
instrumentspecicationisexceeded(e.g.electronicstemperature).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Maintenance:
Duetoexternalinuences,theinstrumentfunction
islimited.Themeasurementisaected,butthemeasuredvalueis
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Status messages

Table of Contents

Other manuals for Vega VEGAPULS 61

Related product manuals