9 Set up with the display and adjustment module
VEGAPULS 6X • Two-wire 4 … 20 mA/HART
66190-EN-221107
Ifnomorereectioncanbedetectedwithinthefocussingrange,a
measuringwindowopens.Thisparameterdenesthetimein"s"
until it opens. This can be the case, for example, in the event of a
levelchangewithoutanevaluablereectionsignalorintheeventof
an echo outside the focussing range with a greater useful echo prob-
ability.
→Asaresult,onreachingthisechowithhighusefulechoprobability,
this is evaluated as a useful echo and output as the current level.
The reference plane for the measurement with radar sensors is
theloweredgeoftheangeorthesealingsurfaceofthethread.
The sensors are calibrated to this reference plane at the factory.
This parameter enables an adaptation of this factory setting, e.g. to
subsequentlyattachedmountingfacilitiessuchasadapteranges,
threaded adapters, etc.
→Apossibleoseterror(constanterrorofthemeasureddistance
over the entire measuring range) is compensated for by this input.
This value in " %" is additional safety below the 0 % adjustment
related to the measuring range.
→Itsupportsthedetectionofanechowhenthevesseliscompletely
empty, even with unfavourable vessel bottom shapes.
This parameter serves to activate/deaxctivate the HART signal in the
output.
This parameter serves to activate/deactivate the Safety Integrity Level
function.
9.5 Save parameter adjustment data
We recommended writing down the adjustment data, e.g. in this op-
erating instructions manual, and archiving them afterwards. They are
thus available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,
the parameter adjustment data can be saved therein. The procedure
is described in menu item " Copy device settings".
SP19 - Time for opening
the focussing range
SP22 - Measured value
oset
SP24 - Factor for ad-
ditional reliability at the
measuring range end
SP HART - HART signal
SP SIL - Safety Integ-
rity Level function
On paper
In the display and adjust-
ment module