19
6 Setup
VEGATOR 636 Ex • Signal conditioning instrument
23446-EN-130627
A-mode B-mode
2 Simulation an empty signal (approx. 1.5 s)
Level relay energised Relay control lamp lights Relaycontrollampo
2 Simulation of an empty signal
Failure lamp Failurelampo Failurelampo
3 Simulation of a full signal (approx. 1.5 s)
Level relay deenergised Relaycontrollampo Relay control lamp lights
3 Simulation of a full signal
Failure lamp Failurelampo Failurelampo
4 Return to the current operating condition (covered/
uncovered)
Check the process of the function test. Take the following criteria into
account for evaluation of the result:
Test passed
If all three switching conditions occur in the correct sequence and the
speciedduration(±20%),thenthetestispassedandtheinstrument
functions correctly.
Test not passed
•
Thespeciedtimesdeviateconsiderablyfromthetable(>3s)
•
One of the switching conditions remains unchanged
•
No start-up of the test - no signal sequence
6.3 Function chart
The following chart provides an overview of the switching conditions
depending on the set mode and the level.
The mode switch on the sensor (if available) must be set to max.
operation.
Sensor (max. opera-
tion)
Signal conditioning instrument
Mode on
the signal
condi-
tioning
instrument
Level Signal
current -
Sensor
Sig-
nal lamp
- Switch-
ing output
(yellow)
Con-
trol lamp
- Failure
(red)
Outputs
Mode A
Overow
protection
approx.
8 mA
Relay ener-
gized
transistor
conducts
Mode A
Overow
protection
approx.
16 mA
Relay de-
energized
transistor
blocks
Evaluation