7Maintenanceandfaultrectication
VEGATOR 636 Ex • Signal conditioning instrument
23446-EN-130627
Error Cause Rectication
The red failure control
lamp (LED) of the signal
conditioning instrument
lights
Current value < 2.3 mA Measure the current value on the signal cable to the
sensor
Check all connections and connection cables to the
sensor
The voltage should be approx. 17 … 20 V
If the value is below 17 V, probably the signal condi-
tioning instrument is defective.
Exchange the signal conditioning instrument or send
it for repair
If the red failure lamp continues to light, separate
the sensor from the connection cable and connect
aresistorof1kΩinsteadonthesignalconditioning
instrument
If the failure lamp continues to light, the signal condi-
tioning instrument is defective
Exchange the signal conditioning instrument or send
it for repair
Should the failure lamp extinguish, you can connect
the sensor again. Separate the signal conditioning
instrument from the connection cable and connect a
resistorof1kΩtothesensorinput
If the failure lamp continues to light, the connection
cable is probably interrupted
Check the connection cable to the sensor
Should the failure lamp extinguish, the sensor will be
defective
Exchange the sensor or send it in for repair
The red failure control
lamp (LED) of the signal
conditioning instrument
lights
Currentvalue>23.2mA Measure the current value on the signal cable to the
sensor
Check all connections and connection cables to the
sensor
If the red failure lamp continues to light, separate
the sensor from the connection cable and connect
aresistorof1kΩinsteadonthesignalconditioning
instrument
If the failure lamp extinguishes, the sensor is defec-
tive. Check the connected sensor
If the failure lamp continues to light, connect the sen-
sor again. Separate signal conditioning instrument
from the connection cable and connect a resistor of
1kΩtothesensorinput.
If the failure lamp extinguishes, this is probably due
to a shortcircuit in the connection cable
Check the connection cable to the sensor
If the failure lamp continues to light, the signal condi-
tioning instrument is defective
Exchange the signal conditioning instrument or send
it for repair
Malfunction during func-
tion test
After pushing the test key,
the switching conditions
do not occur in the correct
sequence or correct du-
ration, e.g. no full signal is
outputted.
Measure the line resistance
If the cable is highly resistive, bring it to a normal
resistance, e.g. check terminals and cable connec-
tions on corrosion