6 Setup
VEGAVIB 61 • Two-wire 8/16 mA
29268-EN-170315
6 Setup
6.1 General information
Theguresinbracketsrefertothefollowingillustrations.
Ontheelectronicsmoduleyouwillndthefollowingdisplayand
adjustment elements:
Potentiometer for adjustment of the density range (1)
DIL switch for mode adjustment - min./max. (2)
Signal lamp (5)
Note:
As a rule, always set the mode before starting to set up VEGAVIB 61 .
If used on a VEGATOR signal conditioning instrument, always set the
mode switch (2) on VEGAVIB 61 to max. mode.
The mode is selected on the signal conditioning instrument with the
mode switch.
The switching output will change if you set one of the two mode
switches afterwards. This could possibly trigger other connected
instruments or devices.
6.2 Adjustment elements
3
4
1
2
5
Fig. 12: Electronics and connection compartment - two-wire output
1 Potentiometer for adjustment of the density range
2 DIL switch for mode adjustment
3 Ground terminal
4 Connection terminals
5 Control lamp
With the potentiometer you can adapt the switching point to the solid.
Itisalreadypresetandmustonlybemodiedinspecialcases.
Function/Conguration
Electronics and terminal
compartment
Adjustment of the density
range (1)