Brakemotors with incorporated brake
Brake connection via motor winding
Y circuit
Terminals 1-2 can be connected directly to the
motor terminals to supply the brake. Compare
the motor/brake voltages to determine whether
the connection is to be made on U1-U2 or U1-
V1.
Terminals 3-4 must be bridged.
Y circuit
Brake
An external power supply can be applied on
terminals 1-2. Check the voltage data on the
rating plate. Terminals 3-4 must be bridged.
For a rapid engagement of the brake (DC-
voltage side tripping) bridge 3-4 can be re-
placed by a contact. The contact must be
tripped simultaneously with the brake power
supply.
āˆ† circuit
In order to provide for the emergency venting
of the brake, e.g. to turn the motor manually,
you can apply a DC voltage source to terminal
1-4 (remove any other wiring before hand and
observe the polarity).
U voltage = = U~ x 0.45
U voltage~see brake voltage on the rating
plate.
BA1-BA4
Brake
1TP1-1TP2
Pre-alarm PTC
2TP1-2TP2
Tripping PTC
U>2.5V not allowed Use tripping device
with PTB number or
marking II(2)G
HE1-HE2
Space heater
TB1-TB2
Temperature monitoring: Microtherm T 10