8.4. Temperature relay configuration
It is possible to configure the built in Relay 1, and Relay 2 (if applicable), to activate and deactivate based on temperature.
See Connecting Temperature Sensors section for compatibility and connection instructions. Confirm the temperature sensors are
correctly connected and reporting temperature in the Device List.
The temperature relay is controlled from Settings Menu → Relay → Function (Relay 1/2) → Temperature. Once enabled, the
Temperature control rules menu will appear in the Relay menu, and inside the temperature sensors that have been detected.
Each temperature sensor can be used to control the relay. Select the temperature sensor you wish to use to control the relay. The
temperature sensors that aren't used will display "No actions". It is possible to enable or disable the temperature relay control for
each temperature sensor within this menu.
In GX products where two relays are available (Cerbo GX & Cerbo-S GX, Ekrano GX), it is possible to have a single temperature
sensor control both relays. It is also possible to have a single relay controlled by multiple different temperature sensors. For
example, a Cerbo GX with 2 lithium battery heat pads, and only using both simultaneously when necessary.
1. In the Relay → Temperature control rules → Temperature sensor menu
2. Enable Relay activation on temperature
3. Assign the relay control to Relay 1
4. Set the Activation value to 5 degrees
5. Set the Deactivation value to 10 degrees
Color Control GX Manual
Page 48 Configuration