Manual VIPA System 200V Chapter 1 Basics and Assembly
HB97E - IM - RE_253-xDPxx - Rev. 12/44 1-17
General data
Profile rail 35mm
Peripheral modules with recessed labelling
Dimensions of the basic enclosure:
1tier width: (HxWxD) in mm: 76x25.4x74 in inches: 3x1x3
2tier width: (HxWxD) in mm: 76x50.8x74 in inches: 3x2x3
Wiring by means of spring pressure connections (CageClamps) at the
front-facing connector, core cross-section 0.08 ... 2.5mm
2
or 1.5 mm
2
(18pole plug)
Complete isolation of the wiring when modules are exchanged
Every module is isolated from the backplane bus
ESD/Burst acc. IEC 61000-4-2 / IEC 61000-4-4 (to level 3)
Shock resistance acc. IEC 60068-2-6 / IEC 60068-2-27 (1G/12G)
Class of protection IP20
Operating temperature: 0 ... +60°C
Storage temperature: -25 ... +70°C
Relative humidity: 5 ... 95% without condensation
Ventilation by means of a fan is not required