Manual VIPA System 200V Chapter 2 Hardware description
HB97E - IM - RE_253-xDPxx - Rev. 12/44 2-5
IM 253-1DP11 - DP-V1 slave - Structure
PROFIBUS (DP-V0, DP-V1)
PROFIBUS DP slave for max. 32 peripheral modules
(max. 16 analog modules)
Max. 244Byte input data and 244Byte output data
Internal diagnostic protocol
Integrated DC 24V power supply for the peripheral modules (3.5A max.)
Supports all PROFIBUS data transfer rates
1 MSAC_C1 connection (Read, Write) with 244Byte data
(4 Byte DP-V1-Header + 240Byte user data)
3 MSAC_C2 connections (Initiale, Read, Write, DataTransport,
Initiate Abort) with each 244Byte data
(4 Byte DP-V1-Header + 240 Byte user data)
[1] LED status indicators
[2] Address selector
(Coding switch)
[3] FO interface
[4] Connector for DC 24V
power supply
Front view
253-1DP11
2
1
4
3
PW
ER
RD
DE
IM 253 DPO
Adr.
X
2
34
VIPA 253-1DP11
DC24V
+
-
1
2
IN
OUT
99
1
2
+ DC 24 V
0 V
+
-
X1
IN
OUT
1
2
Send
Receive
3
4
Send
Receive
LWL
Properties
IM 253DPO
Use as
DP-V1 slave
Interfaces

Related product manuals