Manual VIPA System 200V Chapter 2 Hardware description
HB97E - IM - RE_253-xDPxx - Rev. 12/44 2-5
IM 253-1DP11 - DP-V1 slave - Structure
• PROFIBUS (DP-V0, DP-V1)
• PROFIBUS DP slave for max. 32 peripheral modules
(max. 16 analog modules)
• Max. 244Byte input data and 244Byte output data
• Internal diagnostic protocol
• Integrated DC 24V power supply for the peripheral modules (3.5A max.)
• Supports all PROFIBUS data transfer rates
• 1 MSAC_C1 connection (Read, Write) with 244Byte data
(4 Byte DP-V1-Header + 240Byte user data)
• 3 MSAC_C2 connections (Initiale, Read, Write, DataTransport,
Initiate Abort) with each 244Byte data
(4 Byte DP-V1-Header + 240 Byte user data)
[1] LED status indicators
[2] Address selector
(Coding switch)
[3] FO interface
[4] Connector for DC 24V
power supply
Front view
253-1DP11
2
1
4
3
PW
ER
RD
DE
IM 253 DPO
Adr.
X
2
34
VIPA 253-1DP11
DC24V
+
-
1
2
IN
OUT
99
1
2
+ DC 24 V
0 V
+
-
X1
IN
OUT
1
2
Send
Receive
3
4
Send
Receive
LWL
Properties
IM 253DPO
Use as
DP-V1 slave
Interfaces