Chapter 2 Hardware description Manual VIPA System 200V
2-14 HB97E - IM - RE_253-xDPxx - Rev. 12/44
Order number 253-2DP50
Type IM 253DPR, PROFIBUS-DP slave
Technical data power supply
Power supply (rated value) DC 24 V
Power supply (permitted range) DC 20.4...28.8 V
Reverse polarity protection
9
Current consumption (no-load operation) 80 mA
Current consumption (rated value) 1 A
Inrush current 65 A
I²t 0.85 A²s
Max. current drain at backplane bus 3.5 A
Max. current drain load supply -
Power loss 2.5 W
Status information, alarms, diagnostics
Status display yes
Interrupts yes, parameterizable
Process alarm yes, parameterizable
Diagnostic interrupt yes, parameterizable
Diagnostic functions yes, parameterizable
Diagnostics information read-out none
Supply voltage display green LED
Service Indicator -
Group error display yes
Channel error display none
Hardware configuration
Racks, max. 1
Modules per rack, max. 32
Number of digital modules, max. 32
Number of analog modules, max. 16
Communication
Fieldbus PROFIBUS-DP to EN 50170
Type of interface RS485
Connector Sub-D, 9-pin, female
Topology Linear bus with bus termination at
both ends
Electrically isolated
9
Number of participants, max. 125
Node addresses 1 - 125
Transmission speed, min. 9.6 kbit/s
Transmission speed, max. 12 Mbit/s
Address range inputs, max. 152 Byte
Address range outputs, max. 152 Byte
Number of TxPDOs, max. -
Number of RxPDOs, max. -
Housing
Material PPE / PA 6.6
Mounting Profile rail 35 mm
Mechanical data
Dimensions (WxHxD) 50.8 x 76 x 78 mm
Weight 90 g
Environmental conditions
Operating temperature 0 °C to 60 °C
Storage temperature -25 °C to 70 °C
Certifications
UL508 certification yes
253-2DP50