Manual VIPA System 200V Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44 3-19
V-bus delayed acknowledgment Length: 2
Reading or writing from/to digital modules failed
Byte Bit 7 ... Bit 0
0 2Bh: V-bus delayed acknowledgment
System 200V diagnostic alarm Length: 16
Byte Bit 7 ... Bit 0
0 32h: System 200V diagnostic alarm
1 Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
2 ... 14 Data diagnostic alarm
System 200V process alarm Length: 16
Byte Bit 7 ... Bit 0
0 33h: System 200V process alarm
1 Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
2 ... 14 Process alarm data
New DP address assigned Length: 2
When the slave has received the service with "Set Slave Address" it sends
the respective diagnostic message and re-boots. The slave will then
become available on the bus under the new address.
Byte Bit 7 ... Bit 0
0 3Ch: new DP address has been assigned
Slave status is READY Length: none (internal only)
The READY status of the slave is only used internally and is not transmitted
via the PROFIBUS.
Byte Bit 7 ... Bit 0
0 3Dh: slave status is READY
Slave status is DataExchange Length: none (only internal)
The DataExchange status of the slave is only used internally and is not
transmitted via the PROFIBUS.
Byte Bit 7 ... Bit 0
0 3Eh: slave status is DataExchange
2Bh
32h
33h
3Ch
3Dh
3Eh