Chapter 3 Deployment IM 253DP Manual VIPA System 200V
3-22 HB97E - IM - RE_253-xDPxx - Rev. 12/44
After Power ON, the DP slave executes a self test. It controls its internal
functions and the communication via the backplane bus. After the error free
start-up, the bus coupler switches into the state "ready". In this state, the
DP slave gets its parameters from the DP master and, at valid parameters,
switches into the state "DataExchange" DE (DE is permanently on).
At communication errors at the backplane bus, the PROFIBUS slave
switches into STOP and boots again after app. 2 seconds. As soon as the
test has been completed positive, the RD-LED blinks.
Power On
Stimmen
Projektierungsdaten
mit realem Aufbau
überein?
Parametrier-
fehler?
DP-Slave empfängt
Projektierungdaten
vom DP-Master
ER-LED an
PW-LED an
Initialisierung
DP-Slave setzt
Ausgänge auf "0"
und übernimmt die
eingestellte
PROFIBUS-Adresse
ER-LED erlischt
RD-LED blinkt
RD-LED an
DE-LED an
Ein-/Ausgänge
freigeben
n
Konfigurations-
fehler?
n
j
j
j
ER-LED und
RD-LED blinken
gleichzeitig
ER-LED und
RD-LED blinken
gleichzeitig
Datenaustausch