Manual VIPA System 200V Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44 3-23
IM 253-xDPx1 - DP-V1 slave - Parameters
At deployment of DP slaves presented in this manual there are parameters
for configuration that are individually used for every slave.
At usage of the corresponding GSD for DP-V0 operation you have the
following parameter data:
Byte Bit 7 ... Bit 0 Default
0 Bit 1 ... 0: 0 (fix)
Bit 2: 0 = WD-Timebase 10ms
1 = WD-Timebase 1ms
Bit 4 ... 3: 0 (fix)
Bit 5: 0 = Publisher-Mode not available
1 = Publisher-Mode available
Bit 7 ... 6: 0 (fix)
00h
1 00h (fix) 00h
2 08h (fix) 08h
3 0Ah (fix) 0Ah
4 81h (fix) 81h
5 00h (fix) 00h
6 00h (fix) 00h
7 Bit 0: 0 = Enhanced diagnostic enable
1 = Enhanced diagnostic disable
Bit 1: 0 = Module status enable
1 = Module status disable
Bit 2: 0 = Channel-specific diagnostic enable
1 = Channel-specific diagnostic disable
Bit 3: 0 (fix)
Bit 4: 0 = V0: Manufacturer alarm not available
1 = V0: Manufacturer alarm available
Bit 5: 0 = V0: Diagnostic alarm not available
1 = V0: Diagnostic alarm available
Bit 6: 0 = V0: Process alarm not available
1 = V0: Process alarm available
Bit 7: 0 (fix)
70h
8 Bit 6 ... 0: 0 (fix)
Bit 7: 0 = Data format Motorola
1 = Data format Intel (only at analog modules)
00h
9 ... 12 00h (fix) 00h