Chapter 3 Deployment IM 253DP Manual VIPA System 200V
3-30 HB97E - IM - RE_253-xDPxx - Rev. 12/44
Via the Enhanced diagnostic, which can be activated by parameterization,
you gain information at which slot number (module) an error has occurred.
More detailed information about the error is available via the Module state
and the channel specific diagnostic.
Note!
Note that the length of the enhanced diagnostic of the IM 253-1DP31 -
ECO is limited to 2.
Enhanced diagnostic
Byte Bit 7 ... Bit 0
X Bit 5 ... 0: 000101 (fix) Length of the Enhanced diagnostic*
Bit 7 ... 6: 01 (fix) Code for Enhanced diagnostic
X+1 The bit is set if one of the following occurs:
- a module is removed
- an unconfigured module is inserted
- an inserted module cannot be accessed
- a module reports a diagnostic interrupt
Bit 0: Entry for module on slot 1
Bit 1: Entry for module on slot 2
Bit 2: Entry for module on slot 3
Bit 3: Entry for module on slot 4
Bit 4: Entry for module on slot 5
Bit 5: Entry for module on slot 6
Bit 6: Entry for module on slot 7
Bit 7: Entry for module on slot 8
X+2 Bit 0: Entry for module on slot 9
Bit 1: Entry for module on slot 10
Bit 2: Entry for module on slot 11
Bit 3: Entry for module on slot 12
Bit 4: Entry for module on slot 13
Bit 5: Entry for module on slot 14
Bit 6: Entry for module on slot 15
Bit 7: Entry for module on slot 16
X+3 Bit 0: Entry for module on slot 17
Bit 1: Entry for module on slot 18
Bit 2: Entry for module on slot 19
Bit 3: Entry for module on slot 20
Bit 4: Entry for module on slot 21
Bit 5: Entry for module on slot 22
Bit 6: Entry for module on slot 23
Bit 7: Entry for module on slot 24
X+4 Bit 0: Entry for module on slot 25
Bit 1: Entry for module on slot 26
Bit 2: Entry for module on slot 27
Bit 3: Entry for module on slot 28
Bit 4: Entry for module on slot 29
Bit 5: Entry for module on slot 30
Bit 6: Entry for module on slot 31
Bit 7: Entry for module on slot 32
*) Bit 5 ... 0: 000010 at 253-1DP31 - ECO
Enhanced
diagnostic