Manual VIPA System 200V Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44 3-53
To be compatible with the Siemens SIMATIC Manager, you have to
execute the following steps for the System 200V:
Start the Hardware configurator from Siemens
Install the GSD-file vipa_21x.gsd
Project a CPU 315-2DP with DP master (master address 2)
Add a PROFIBUS slave "VIPA_CPU21x" with address 1.
Include the CPU 214-1BA03 at slot 0.
Include the DP master 208-1DP01 at slot 1.
To connect your IM 253DP, you have to execute the following steps after
including the GSD-file vipa0550.gsd:
Add the PROFIBUS slave "VIPA_DP200V_2" with address 3.
You will find the DP slave in the hardware catalog from Siemens at:
PROFIBUS DP>Additional field devices>I/O>VIPA_System_200V
Include the digital output module 222-1BF00 at slot 0.
Assign the output address 0.
Engineering
IM 208DP